Yeoman Exe MidiConventional Flue Coal Effect StoveWith upgradeable control valveInstructions for Use,Installation and ServicingFor use in GB, IE (Grea
CABA = 643mmB = 43mmC = 12mmAR060414.2 This appliance must not be installed in a room that contains a bath or shower.4.3 The stove is not suitable f
112.7 The stove is fitted with the Gazco Flue Sure System, which will act to cut off the gas supply to the appliance in the event of incorrect operat
123.5 Check the pull of the flue system by applying a lighted smoke pellet to the flue system opening. If there is a definite flow into the chimney,
13AR036084.8 Place the log retainer in the two guides as shown in Diagram 9.AR20769 FOR CLARITY, THE FOLLOWING LOG ARRANGEMENT DIAGRAMS DO NOT INCLU
14INSTALLATION INSTRUCTIONSCOMMISSIONING1. COMMISSIONING After connecting the gas pipe to the stove:1.1 PURGE THE SUPPLY PIPE to dispel any debris t
15IGNITION FUNCTIONAL CHECK 1PILOT WILL NOT LIGHTEnsure there is no debris around the pilot assembly, (e.g. soot, etc.) which could short the spark,
16PILOT WILL NOT STAY LIT OR FIRE GOES OUT IN USEEnsure there is no debris around the pilot assembly, e.g. coal, soot etc. which could short the spark
172.4 Remove the two screws at the back of the firebox and lift the burner unit clean (see Diagram 3).AR144233. PILOT UNIT3.1 Follow the procedure f
183.3 The pilot unit can now be removed by undoing the two screws (see Diagram 6).AR144563.4 Reassemble in reverse order, do not overtighten. NOTE:
196.3 Undo the single screw that secures the left hand side of the control cover (see Diagram 10).10AR09156.4 To release the right hand side of the
2CONTENTSCOVERING THE FOLLOWING MODELS:YM-N9171FL / YM-N9171LCYM-P9171FL / YM-P9171LC PAGEAPPLIANCE COMMISSIONING CHECKLIST 3 USER INSTRUCTIONS 4I
209. GAZCO FLUE SURE SYSTEM9.1 Open the door and remove the ceramics, placing them carefully to one side. Undo the two screws in the back of the fire
21 11. CHANGING BETWEEN GAS TYPES In order to change between gas types it will be necessary to change the following items: - Pilot Unit - Control V
22SERVICE RECORDS1ST SERVICE 2ND SERVICEDate of Service: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Date of Service: ...
A division of Stovax LtdFalcon Road, Sowton Industrial Estate, Exeter, Devon, England EX2 7LFTel: (01392) 474500 Fax: (01392) 219932E-mail: yeoman@s
3FLUE CHECK PASS FAIL1. Flue is correct for appliance 2. Flue flow test 3. Spillage test GAS CHECK 1. Gas soundness & let by test2. Standin
4USER INSTRUCTIONS1.7 The manufacturer considers the full outer casing of this stove to be a working surface which becomes hot when the stove is lit.
52. LIGHTING THE STOVE2.1 The control valve is on the right-hand side at the foot of the stove. It has two controls: —The right-hand knob controls t
65. CLEANING THE STOVE Advice on Handling and Disposal of Fire Ceramics5.1 The fuel effect logs and embers in this stove are made from Refractory Ce
7HEADING6. FUEL BED ARRANGEMENT6.1 Place the flame baffle onto the burner and push against the rear tray lip (see Diagram 5).AR03595Spacer brackets6.
8AR0364116.8 Replace the glass frame using the 6 x frame fixing screws (see Diagram 4) and close door.7. GAZCO FLUE SURE SYSTEM The stove is fitt
9INSTALLATION INSTRUCTIONSTECHNICAL SPECIFICATIONCovering the following models:Yeoman Exe MidiYM-N9171FL / YM-N9171LCYM-P9171FL / YM-P9171LC1 x Stove